Name:

Low-smoke halogen-free power cable

No.:
Affiliate classification:
没有此类产品
I want to make an inquiry
Detail

It is suitable for use in high-rise buildings, centralized personnel and high environmental protection requirements.

The flame retardant performance is superior, the smoke released during combustion is less, the visibility is high, the amount of harmful gas released is less, and it is convenient for people to evacuate; the corrosiveness of combustion gas is small, and the damage of multi-instrument equipment is avoided.

 

Low-smoke halogen-free power cable 

 

 

Product introduction

 

Low smoke halogen-free wires and cables produce very small amount of smoke under the condition of flame combustion, which releases gas without halogen and non-toxic. When fire occurs, it can greatly reduce the harm to instruments/equipment and human body, so it is widely used in high-rise buildings/hospitals, large libraries, stadiums, Disaster Prevention Command and dispatch buildings, stations and civil airports. Passenger waiting rooms, key cultural relics protection sites and subway, underground shopping malls or densely populated public places.

 

Our company develops and produces plastic insulated wires and cables with rated voltage of 35KV and below. Their performance not only meets the requirements of GB/T 12766-2008, GB/T 5023-2008 and GB/T 9330-2008, but also forms a series of flame-retardant, fire-resistant, especially low smoke and halogen-free properties, which meet the national standards GB/T 17650-1-2-1998 and GB/T 17651.1-2-1998. At the national level, sci tech novelty searches have reached the domestic advanced level of similar products.

 

Product type and name

 

Model

Name

Flame retardancy

WDZ-YJ(F)Y

(Irradiated) XLPE insulated low-smoke halogen-free flame-retarding PO sheathed power cable 

A

B

C

WDZ-YJ(F)Y23

(Irradiated) XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed power cable 

WDZ-YJ(F)Y33

WDZ-YJ(F)Y43

(Irradiated) XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed power cable 

WDZ-YJ(F)Y

(Irradiated) XLPE insulated low-smoke halogen-free flame-retarding PO sheathed power cable 

WDZN-YJ(F)Y

(Irradiated) XLPE insulated low-smoke halogen-free flame-retarding PO sheathed fireproof power cable 

WDZN-YJ(F)Y23

(Irradiated) XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed fireproof power cable 

WDZ-YJY

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed power cable 

WDZ-YJY23

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed power cable 

WDZ-YJY33

WDZ-YJY43

XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed power cable

WDZ-YJY

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed power cable

WDZN-YJY

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed fireproof power cable 

WDZN-YJY23

XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed fireproof power cable 

WDZ-KYJ(F)Y

(Irradiated) XLPE insulated low-smoke halogen-free flame-retarding PO sheathed control cable 

A

B

C

WDZ-KYJ(F)Y23

(Irradiated) XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJ(F)YP

Irradiated) XLPE insulated copper-wire braided shield low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJ(F)YP2

(Irradiated) XLPE insulated copper-tape shielded low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJ(F)Y33

(Irradiated) XLPE insulated steel-wire armoured low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZN-KYJ(F)Y

(Irradiated) XLPE insulated low-smoke halogen-free flame-retarding PO sheathed fireproof control cable 

WDZN-KYJ(F)Y23

rradiated) XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed fireproof control cable

WDZ-KYJY

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJY23

XLPE insulated steel-tape armoured low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJYP

XLPE insulated copper-wire braided shield low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJYP2

XLPE insulated copper-tape shielded low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZ-KYJY33

XLPE insulated steel-wire armoured low-smoke halogen-free flame-retarding PO sheathed control cable 

WDZN-KYJY

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed fireproof control cable 

WDZN-KYJY23

XLPE insulated low-smoke halogen-free flame-retarding PO sheathed fireproof control cable 

WDZ-BYJ(F)

Low-smoke halogen-free flame-retarding XLPO insulated wire 

WDZ-BY

Low-smoke halogen-free flame-retarding PO insulated wire 

WDZN-BYJ(F)

Low-smoke halogen-free flame-retarding XLPO insulated fireproof wire 

WDZN-BY

Low-smoke halogen-free flame-retarding PO insulated fireproof wire

 

Product technical performance

1. The maximum operating temperature and the maximum short-circuited (no more than 5 seconds) temperature of the wire and cable conductor: 70°Cfor the low-smoke halogen-free PVC insulated cable, with the maximum short-circuited temperature no higher than 160°C; 90°Cfor the XLPE insulated cable, 80°Cfor the thermoplastic low-smoke halogen-free PO insulated cable, with the maximum short-circuited temperature no higher than 250°C; 105°Cand 125°Cfor the irradiated XLPE insulated cable, with the maximum short-circuited temperature no higher than 250°C.

2. The installation conditions and allowable continuous current-carrying capacity of the low-smoke halogen-free cable are the same as that of the non-low-smoke halogen-free cable.
3. The cable and wire have low-smoke, halogen-free, flame-retarding and fireproof properties when burning, with specific indicators as shown in the

 

following figure. 

Serial number

Test project

Standard requirements

1

Single vertical burning test of wire and cable
- Distance between the lower edge of upper bracket and the starting point of carbonized part
- the distance that the combustion extends downward to the lower edge of the upper bracket 

≥50mm

≤540mm

2

Standard requirements

≤2.5m

3

Fire resistance test

When burning for 90 min, apply the rated voltage and find that the 2A fuse is not fused 

4

PH value

≥4.3

5

Weighted value of conductivity

≤10µs/mm

6

Cable smoke density test - the minimum light transmittance 

≤60%

 

Corresponding parameter set not found, please add it in property template of background