Overhead insulated cable
Keywords:
Overhead insulated cable
Category:
Summary:

Tel:
Overhead insulated cable
It is mainly used for overhead fixed laying, line drawing and other places.
Overhead insulated cables can reduce laying gap, save line corridors, reduce power supply accidents and ensure personal safety.
Overhead insulated cables with the rated voltage of 1 kV and below
purpose
This product is applicable to the overhead cables with copper core, aluminum core or aluminum alloy core weatherable polyvinyl chloride (PVC), polyethylene (PE) and crosslinked polyethylene (XLPE) insulations for the overhead power lines with the AC rated voltage U0/U of 0.6/1kv and below.
Applicable conditions
1. The rated voltage U0/U is 0.6/1 kV.
2. The long-term allowable operating temperature of the cable conductor: The temperature of PVC and PE insulations shall not exceed 70°C; the temperature of XLPE insulation shall not exceed 90°C;
3. The cable laying temperature shall not be lower than -20°C.
4. The allowable bending radius of cable: For the cable with the outer diameter lower than 25 mm, the radius shall not be lower than 4D. For the cable with the outer diameter of 25 mm and above, the radius shall not be lower than 6D.
Type and name
Model |
Name |
Main uses |
JKV-0.6/1kV |
Copper-core PVC insulated overhead cable with the rated voltage of 0.6/1 kV |
Overhead fixed laying, leading line, etc. |
JKLV-0.6/1kV |
Overhead fixed laying, leading service wire, etc. |
|
JKLHV-0.6/1kV |
Aluminum-core PVC insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKY-0.6/1kV |
Aluminum-alloy-core PVC insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKLY-0.6/1kV |
Copper-core PE insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKLHY-0.6/1kV |
Aluminum-core PE insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKYJ-0.6/1kV |
Aluminum-core PE insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKLYJ-0.6/1kV |
Copper-core XLPE insulated overhead cable with the rated voltage of 0.6/1 kV |
|
JKLHYJ-0.6/1kV |
Aluminum-core XLPE insulated overhead cable with the rated voltage of 0.6/1 kV |
Delivery requirements
1. The goods are delivered at any length according to the agreement of both parties.
2. Cables shall be neatly wound on the delivery tray, their ends shall be sealed well, and the length stretching out of the cable tray shall meet the test requirements. Only cables of the same type and specification are allowed to be wound on a delivery tray.。
33. In case of no agreement between both parties, the provisions of GB/T 12527-2 shall be implemented。
10 KV XLPE insulated overhead cable
purpose
This product is applicable to overhead power lines with the AC rated voltage U(Um) of 10 (12) kV.
Applicable conditions
1. The maximum long-term allowable operating temperature of the cable conductor is 90°C.
2. The laying temperature is not less than -20 C.
3. The maximum temperature of conductor should not be greater than 250 C when short circuit (the longest duration does not exceed 5 seconds).
Model specification
Model |
Name |
Main uses |
JKYJ |
Copper-core XLPE insulated overhead cable |
Overhead fixed laying, and flexible copper-core products used for downlead of transformer. During cable erection, a certain distance shall be reserved between the cable and tree; frequent contact between the cable and tree is allowable during cable operation |
JKTRYJ |
Flexible copper-core XLPE insulated overhead cable |
|
JKLYJ |
Aluminum-core XLPE insulated overhead cable |
|
JKLHYJ |
Aluminum-alloy-core XLPE insulated overhead cable |
|
JKY |
Copper-core PE insulated overhead cable |
|
JKTRY |
Copper-core PE insulated overhead cable |
|
JKLY |
Aluminum-core PE insulated overhead cable |
|
JKLHY |
Aluminum-alloy-core PE insulated overhead cable |
|
JKLYJ/B |
Aluminum-core natural-colour XLPE insulated overhead cable |
Overhead fixed laying During cable erection, a certain distance shall be reserved between the cable and tree; frequent contact between the cable and tree is allowable during cable operation |
JKLHYJ/B |
Aluminum-alloy-core natural-colour XLPE insulated overhead cable |
|
JKLYJ/Q |
Aluminum-core lightweight XLPE insulated overhead cable |
Overhead fixed laying During cable erection, a certain distance shall be reserved between the cable and tree; short contact between the cable and tree is allowable during cable operation |
JKLHYJ/Q |
Aluminum-alloy-core lightweight XLPE insulated overhead cable |
|
JKLY/Q |
luminum-core lightweight PE insulated overhead cable |
|
JKLHY/Q |
Aluminum-alloy-core lightweight PE insulated overhead cable |
Cargo requirements
1, according to the agreement between the two sides, delivery at any length.
2. The cables should be neatly wound on the delivery tray, and the ends should be sealed well. The length of the exposed cable tray should meet the test requirements. Only the same type of cable can be wound on one delivery tray.
3, when there is no agreement between the two parties, the provisions of the GB/T14049-2008 standard shall be implemented.